Cable size for 200 A over 5 m, DC

For 200 A over 5 m on a 12 V DC supply, use at least 150 mm² (300 kcmil) copper cable, protected by a 250 A fuse. Voltage drop: 2.5%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
1 m70 mm² (3/0 AWG)1.1%
2 m70 mm² (3/0 AWG)2.1%
3 m95 mm² (4/0 AWG)2.4%
5 m150 mm² (300 kcmil)2.5%
10 m2 × 150 mm² (300 kcmil)2.5%
150 mm²
300 kcmil
250 A
Fuse
2.5%
Voltage drop
2× 6m
Red + black

Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.

How the cable runs
Use at least150 mm²300 kcmil
Fuse250 A
Voltage drop2.5% · 0.3 V
Current200 A
Cable carries up to480 A

The distance decides this size: 70 mm² would stay cool enough, but over 5 m it loses too much voltage.

Cores

2 cores (+ and −), or two single cables, red and black

🛒 To buy: 6 m of red and 6 m of black 150 mm² cable (your 5 m run plus 10% spare, rounded up). Red for positive, black for negative.

Which cable

Typical price for 2 × 6 m: £580–£820

Tinned flexible battery cable (ISO 6722 / SAE J1127)

Vans and boats: resists vibration and corrosion.

🔎 Find it online
Welding cable (H01N2-D)

Very flexible, for heavy battery and inverter leads.

🔎 Find it online

Rough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.

  • Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.