Cable size for 200 A over 10 m, DC
For 200 A over 10 m on a 12 V DC supply, use at least 2 × 150 mm² (300 kcmil) copper cable, protected by a 250 A fuse. Voltage drop: 2.5%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 2×150 mm²
- 300 kcmil
- 250 A
- Fuse
- 2.5%
- Voltage drop
- 4× 11m
- Red + black
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
The distance decides this size: 70 mm² would stay cool enough, but over 10 m it loses too much voltage.
Cores
2 cores (+ and −), or two single cables, red and black
🛒 To buy: 22 m of red and 22 m of black 150 mm² cable (your 10 m run plus 10% spare, rounded up). Red for positive, black for negative. That is 2 cables side by side for each line, so the length is already multiplied.
Which cable
Typical price for 4 × 11 m: £2,100–£3,000
Vans and boats: resists vibration and corrosion.
🔎 Find it onlineVery flexible, for heavy battery and inverter leads.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- This needs 2 cables in parallel per conductor, all of equal length and size.
- Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.