Cable size for 200 A over 2 m, DC

For 200 A over 2 m on a 12 V DC supply, use at least 70 mm² (3/0 AWG) copper cable, protected by a 250 A fuse. Voltage drop: 2.1%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
1 m70 mm² (3/0 AWG)1.1%
2 m70 mm² (3/0 AWG)2.1%
3 m95 mm² (4/0 AWG)2.4%
5 m150 mm² (300 kcmil)2.5%
10 m2 × 150 mm² (300 kcmil)2.5%
70 mm²
3/0 AWG
250 A
Fuse
2.1%
Voltage drop
2× 3m
Red + black

Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.

How the cable runs
Use at least70 mm²3/0 AWG
Fuse250 A
Voltage drop2.1% · 0.26 V
Current200 A
Cable carries up to315 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine. The same amps need the same cable at any voltage: heat depends on current. What changes with voltage is how many amps a load draws: switch the unit to W and the size follows the voltage (9,600 W is 200 A at 48 V but 800 A at 12 V).

Cores

2 cores (+ and −), or two single cables, red and black

🛒 To buy: 3 m of red and 3 m of black 70 mm² cable (your 2 m run plus 10% spare, rounded up). Red for positive, black for negative.

Which cable

Typical price for 2 × 3 m: £150–£240

Tinned flexible battery cable (ISO 6722 / SAE J1127)

Vans and boats: resists vibration and corrosion.

🔎 Find it online
Welding cable (H01N2-D)

Very flexible, for heavy battery and inverter leads.

🔎 Find it online

Rough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.

  • Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.