Cable size for 80 A over 100 m, three-phase
For 80 A over 100 m on a 400 V three-phase supply, use at least 35 mm² (1 AWG) copper cable, protected by a 100 A breaker. Voltage drop: 2.2%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 35 mm²
- 1 AWG
- 100 A
- Breaker
- 2.2%
- Voltage drop
- 111m
- 5-core to buy
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)
🛒 To buy: 111 m of 5-core 35 mm² cable (your 100 m run plus 10% spare, rounded up).
Which cable
Typical price for 111 m: £4,200–£6,700
Fixed wiring clipped to walls indoors.
🔎 Find it onlineMachines, workshops and anything that moves or vibrates.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.