Cable size for 80 A over 100 m, single-phase
For 80 A over 100 m on a 230 V single-phase supply, use at least 35 mm² (1 AWG) copper cable, protected by a 100 A breaker. Voltage drop: 4.5%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 35 mm²
- 1 AWG
- 100 A
- Breaker
- 4.5%
- Voltage drop
- 111m
- 3-core to buy
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
The distance decides this size: 25 mm² would stay cool enough, but over 100 m it loses too much voltage.
Cores
3 cores: line, neutral and earth
🛒 To buy: 111 m of 3-core 35 mm² cable (your 100 m run plus 10% spare, rounded up).
Which cable
Typical price for 111 m: £2,800–£4,400
Fixed wiring clipped to walls indoors.
🔎 Find it onlineMachines, workshops and anything that moves or vibrates.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.