Cable size for 50 A over 1 m, DC
For 50 A over 1 m on a 12 V DC supply, use at least 10 mm² (8 AWG) copper cable, protected by a 70 A fuse. Voltage drop: 1.9%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 10 mm²
- 8 AWG
- 70 A
- Fuse
- 1.9%
- Voltage drop
- 2 m
- 2-core cable
How the cable runs
Use at least10 mm²8 AWG
Fuse70 A
Voltage drop1.9% · 0.23 V
Current50 A
Cable carries up to86 A
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
2 cores (+ and −), or two single cables, red and black
Which cable
Tinned flexible battery cable (ISO 6722 / SAE J1127)
Vans and boats: resists vibration and corrosion.
Welding cable (H01N2-D)
Very flexible, for heavy battery and inverter leads.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.