Cable size for 30 A over 3 m, DC
For 30 A over 3 m on a 12 V DC supply, use at least 16 mm² (6 AWG) copper cable, protected by a 40 A fuse. Voltage drop: 2.1%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 16 mm²
- 6 AWG
- 40 A
- Fuse
- 2.1%
- Voltage drop
- 4 m
- 2-core cable
How the cable runs
Use at least16 mm²6 AWG
Fuse40 A
Voltage drop2.1% · 0.25 V
Current30 A
Cable carries up to114 A
The distance decides this size: 4 mm² would stay cool enough, but over 3 m it loses too much voltage.
Cores
2 cores (+ and −), or two single cables, red and black
Which cable
Tinned flexible battery cable (ISO 6722 / SAE J1127)
Vans and boats: resists vibration and corrosion.
Welding cable (H01N2-D)
Very flexible, for heavy battery and inverter leads.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.