WireTheSun

Cable size for 30 A over 2 m, DC

For 30 A over 2 m on a 12 V DC supply, use at least 10 mm² (6 AWG) copper cable, protected by a 40 A fuse. Voltage drop: 2.2%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
1 m4 mm² (10 AWG)2.8%
2 m10 mm² (6 AWG)2.2%
3 m16 mm² (4 AWG)2.1%
5 m25 mm² (3 AWG)2.3%
10 m50 mm² (1/0 AWG)2.3%
10 mm²
6 AWG
40 A
Fuse
2.2%
Voltage drop
2× 3m
Red + black

Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.

How the cable runs
Use at least10 mm²6 AWG
Fuse40 A
Voltage drop2.2% · 0.27 V
Current30 A
Cable carries up to86 A

The distance decides this size: 4 mm² would stay cool enough, but over 2 m it loses too much voltage.

Cores

2 cores (+ and −), or two single cables, red and black

🛒 To buy: 3 m of red and 3 m of black 10 mm² cable (your 2 m run plus 10% spare, rounded up). Red for positive, black for negative.

Which cable

Typical price for 2 × 3 m: £21–£48

Tinned flexible battery cable (ISO 6722 / SAE J1127)

Vans and boats: resists vibration and corrosion.

🔎 Find it online
Welding cable (H01N2-D)

Very flexible, for heavy battery and inverter leads.

🔎 Find it online

Rough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.

  • Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.

Planning a whole solar system?Describe it and we size every cable, fuse and part, with a wiring diagram.