Cable size for 25 A over 10 m, three-phase

For 25 A over 10 m on a 400 V three-phase supply, use at least 4 mm² (12 AWG) copper cable, protected by a 32 A breaker. Voltage drop: 0.6%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m4 mm² (12 AWG)0.6%
20 m4 mm² (12 AWG)1.2%
30 m4 mm² (12 AWG)1.8%
50 m4 mm² (12 AWG)3%
100 m6 mm² (10 AWG)4.1%
4 mm²
12 AWG
32 A
Breaker
0.6%
Voltage drop
11 m
5-core cable
How the cable runs
Use at least4 mm²12 AWG
Breaker32 A
Voltage drop0.6% · 2.44 V
Current25 A
Cable carries up to32 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)

Which cable

NYM-J / XVB / 5-core LSZH

Fixed wiring clipped to walls indoors.

H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.