Cable size for 25 A over 100 m, three-phase
For 25 A over 100 m on a 400 V three-phase supply, use at least 6 mm² (10 AWG) copper cable, protected by a 32 A breaker. Voltage drop: 4.1%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 6 mm²
- 10 AWG
- 32 A
- Breaker
- 4.1%
- Voltage drop
- 111 m
- 5-core cable
How the cable runs
Use at least6 mm²10 AWG
Breaker32 A
Voltage drop4.1% · 16.24 V
Current25 A
Cable carries up to41 A
The distance decides this size: 4 mm² would stay cool enough, but over 100 m it loses too much voltage.
Cores
5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)
Which cable
NYM-J / XVB / 5-core LSZH
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.