Cable size for 10 A over 20 m, single-phase

For 10 A over 20 m on a 230 V single-phase supply, use at least 1.5 mm² (16 AWG) copper cable, protected by a 13 A breaker. Voltage drop: 2.6%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m1.5 mm² (16 AWG)1.3%
20 m1.5 mm² (16 AWG)2.6%
30 m1.5 mm² (16 AWG)3.9%
50 m2.5 mm² (14 AWG)3.9%
100 m4 mm² (12 AWG)4.9%
1.5 mm²
16 AWG
13 A
Breaker
2.6%
Voltage drop
22 m
3-core cable
How the cable runs
Use at least1.5 mm²16 AWG
Breaker13 A
Voltage drop2.6% · 6 V
Current10 A
Cable carries up to20 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

3 cores: line, neutral and earth

Which cable

Twin & Earth 6242Y (UK) or NYM-J (Europe)

Fixed wiring clipped to walls indoors.

H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.