Cable size for 10 A over 100 m, single-phase
For 10 A over 100 m on a 230 V single-phase supply, use at least 4 mm² (12 AWG) copper cable, protected by a 13 A breaker. Voltage drop: 4.9%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 4 mm²
- 12 AWG
- 13 A
- Breaker
- 4.9%
- Voltage drop
- 111 m
- 3-core cable
How the cable runs
Use at least4 mm²12 AWG
Breaker13 A
Voltage drop4.9% · 11.25 V
Current10 A
Cable carries up to36 A
The distance decides this size: 1.5 mm² would stay cool enough, but over 100 m it loses too much voltage.
Cores
3 cores: line, neutral and earth
Which cable
Twin & Earth 6242Y (UK) or NYM-J (Europe)
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.