WireTheSunCommon cable sizes

Cable size for 100 A over 10 m, single-phase

For 100 A over 10 m on a 230 V single-phase supply, use at least 35 mm² (2 AWG) copper cable, protected by a 125 A breaker. Voltage drop: 0.6%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m35 mm² (2 AWG)0.6%
20 m35 mm² (2 AWG)1.1%
30 m35 mm² (2 AWG)1.7%
50 m35 mm² (2 AWG)2.8%
100 m50 mm² (1 AWG)3.9%
35 mm²
2 AWG
125 A
Breaker
0.6%
Voltage drop
11 m
3-core cable
How the cable runs
Use at least35 mm²2 AWG
Breaker125 A
Voltage drop0.6% · 1.29 V
Current100 A
Cable carries up to138 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

3 cores: line, neutral and earth

Which cable

Twin & Earth 6242Y (UK) or NYM-J (Europe)

Fixed wiring clipped to walls indoors.

H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.

Planning a whole solar system?Describe it and we size every cable, fuse and part, with a wiring diagram.