Cable size for 100 A over 100 m, single-phase
For 100 A over 100 m on a 230 V single-phase supply, use at least 50 mm² (1 AWG) copper cable, protected by a 125 A breaker. Voltage drop: 3.9%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 50 mm²
- 1 AWG
- 125 A
- Breaker
- 3.9%
- Voltage drop
- 111 m
- 3-core cable
How the cable runs
Use at least50 mm²1 AWG
Breaker125 A
Voltage drop3.9% · 9 V
Current100 A
Cable carries up to168 A
The distance decides this size: 35 mm² would stay cool enough, but over 100 m it loses too much voltage.
Cores
3 cores: line, neutral and earth
Which cable
Twin & Earth 6242Y (UK) or NYM-J (Europe)
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.