Cable size for 63 A over 20 m, three-phase
For 63 A over 20 m on a 400 V three-phase supply, use at least 25 mm² (4 AWG) copper cable, protected by a 80 A breaker. Voltage drop: 0.5%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 25 mm²
- 4 AWG
- 80 A
- Breaker
- 0.5%
- Voltage drop
- 22 m
- 5-core cable
How the cable runs
Use at least25 mm²4 AWG
Breaker80 A
Voltage drop0.5% · 1.96 V
Current63 A
Cable carries up to96 A
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)
Which cable
NYM-J / XVB / 5-core LSZH
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.