WireTheSunCommon cable sizes

Cable size for 50 A over 100 m, three-phase

For 50 A over 100 m on a 400 V three-phase supply, use at least 16 mm² (6 AWG) copper cable, protected by a 63 A breaker. Voltage drop: 3%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m16 mm² (6 AWG)0.3%
20 m16 mm² (6 AWG)0.6%
30 m16 mm² (6 AWG)0.9%
50 m16 mm² (6 AWG)1.5%
100 m16 mm² (6 AWG)3%
16 mm²
6 AWG
63 A
Breaker
3%
Voltage drop
111 m
5-core cable
How the cable runs
Use at least16 mm²6 AWG
Breaker63 A
Voltage drop3% · 12.18 V
Current50 A
Cable carries up to76 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)

Which cable

NYM-J / XVB / 5-core LSZH

Fixed wiring clipped to walls indoors.

H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.