Cable size for 40 A over 20 m, single-phase
For 40 A over 20 m on a 230 V single-phase supply, use at least 10 mm² (8 AWG) copper cable, protected by a 50 A breaker. Voltage drop: 1.6%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 10 mm²
- 8 AWG
- 50 A
- Breaker
- 1.6%
- Voltage drop
- 22 m
- 3-core cable
How the cable runs
Use at least10 mm²8 AWG
Breaker50 A
Voltage drop1.6% · 3.6 V
Current40 A
Cable carries up to63 A
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
3 cores: line, neutral and earth
Which cable
Twin & Earth 6242Y (UK) or NYM-J (Europe)
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.