WireTheSunCommon cable sizes

Cable size for 30 A over 1 m, DC

For 30 A over 1 m on a 24 V DC supply, use at least 4 mm² (12 AWG) copper cable, protected by a 40 A fuse. Voltage drop: 1.4%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
1 m4 mm² (12 AWG)1.4%
2 m4 mm² (12 AWG)2.8%
3 m6 mm² (10 AWG)2.8%
5 m10 mm² (8 AWG)2.8%
10 m25 mm² (4 AWG)2.3%
4 mm²
12 AWG
40 A
Fuse
1.4%
Voltage drop
2 m
2-core cable
How the cable runs
Use at least4 mm²12 AWG
Fuse40 A
Voltage drop1.4% · 0.34 V
Current30 A
Cable carries up to49 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

2 cores (+ and −), or two single cables, red and black

Which cable

Tinned flexible battery cable (ISO 6722 / SAE J1127)

Vans and boats: resists vibration and corrosion.

Welding cable (H01N2-D)

Very flexible, for heavy battery and inverter leads.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.

Planning a whole solar system?Describe it and we size every cable, fuse and part, with a wiring diagram.