Cable size for 25 A over 10 m, single-phase

For 25 A over 10 m on a 230 V single-phase supply, use at least 4 mm² (10 AWG) copper cable, protected by a 32 A breaker. Voltage drop: 1.2%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m4 mm² (10 AWG)1.2%
20 m4 mm² (10 AWG)2.4%
30 m4 mm² (10 AWG)3.7%
50 m6 mm² (8 AWG)4.1%
100 m10 mm² (6 AWG)4.9%
4 mm²
10 AWG
32 A
Breaker
1.2%
Voltage drop
11m
3-core to buy

Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.

How the cable runs
Use at least4 mm²10 AWG
Breaker32 A
Voltage drop1.2% · 2.81 V
Current25 A
Cable carries up to36 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

3 cores: line, neutral and earth

🛒 To buy: 11 m of 3-core 4 mm² cable (your 10 m run plus 10% spare, rounded up).

Which cable

Typical price for 11 m: £39–£66

Twin & Earth 6242Y (UK) or NYM-J (Europe)

Fixed wiring clipped to walls indoors.

🔎 Find it online
H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

🔎 Find it online

Rough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.