Cable size for 20 A over 50 m, three-phase
For 20 A over 50 m on a 400 V three-phase supply, use at least 4 mm² (12 AWG) copper cable, protected by a 25 A breaker. Voltage drop: 2.4%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 4 mm²
- 12 AWG
- 25 A
- Breaker
- 2.4%
- Voltage drop
- 56 m
- 5-core cable
How the cable runs
Use at least4 mm²12 AWG
Breaker25 A
Voltage drop2.4% · 9.74 V
Current20 A
Cable carries up to32 A
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)
Which cable
NYM-J / XVB / 5-core LSZH
Fixed wiring clipped to walls indoors.
H07RN-F (rubber, flexible)
Machines, workshops and anything that moves or vibrates.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.