Cable size for 20 A over 1 m, DC

For 20 A over 1 m on a 48 V DC supply, use at least 1.5 mm² (16 AWG) copper cable, protected by a 25 A fuse. Voltage drop: 1.2%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
1 m1.5 mm² (16 AWG)1.2%
2 m1.5 mm² (16 AWG)2.5%
3 m2.5 mm² (14 AWG)2.2%
5 m4 mm² (12 AWG)2.3%
10 m10 mm² (8 AWG)1.9%
1.5 mm²
16 AWG
25 A
Fuse
1.2%
Voltage drop
2 m
2-core cable
How the cable runs
Use at least1.5 mm²16 AWG
Fuse25 A
Voltage drop1.2% · 0.6 V
Current20 A
Cable carries up to28 A

Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.

Cores

2 cores (+ and −), or two single cables, red and black

Which cable

Tinned flexible battery cable (ISO 6722 / SAE J1127)

Vans and boats: resists vibration and corrosion.

Welding cable (H01N2-D)

Very flexible, for heavy battery and inverter leads.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.