Cable size for 20 A over 10 m, DC
For 20 A over 10 m on a 24 V DC supply, use at least 16 mm² (4 AWG) copper cable, protected by a 25 A fuse. Voltage drop: 2.3%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 16 mm²
- 4 AWG
- 25 A
- Fuse
- 2.3%
- Voltage drop
- 2× 11m
- Red + black
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
The distance decides this size: 1.5 mm² would stay cool enough, but over 10 m it loses too much voltage.
Cores
2 cores (+ and −), or two single cables, red and black
🛒 To buy: 11 m of red and 11 m of black 16 mm² cable (your 10 m run plus 10% spare, rounded up). Red for positive, black for negative.
Which cable
Typical price for 2 × 11 m: £110–£200
Vans and boats: resists vibration and corrosion.
🔎 Find it onlineVery flexible, for heavy battery and inverter leads.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.