Cable size for 150 A over 1 m, DC
For 150 A over 1 m on a 48 V DC supply, use at least 35 mm² (1 AWG) copper cable, protected by a 200 A fuse. Voltage drop: 0.4%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 35 mm²
- 1 AWG
- 200 A
- Fuse
- 0.4%
- Voltage drop
- 2× 2m
- Red + black
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine. The same amps need the same cable at any voltage: heat depends on current. What changes with voltage is how many amps a load draws: switch the unit to W and the size follows the voltage (9,600 W is 200 A at 48 V but 800 A at 12 V).
Cores
2 cores (+ and −), or two single cables, red and black
🛒 To buy: 2 m of red and 2 m of black 35 mm² cable (your 1 m run plus 10% spare, rounded up). Red for positive, black for negative.
Which cable
Typical price for 2 × 2 m: £44–£80
Vans and boats: resists vibration and corrosion.
🔎 Find it onlineVery flexible, for heavy battery and inverter leads.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- Sized for runs outside the engine space. In an engine space, or bundled with other cables, choose the next size up.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.