Cable size for 13 A over 10 m, single-phase
For 13 A over 10 m on a 230 V single-phase supply, use at least 2.5 mm² (12 AWG) copper cable, protected by a 20 A breaker. Voltage drop: 1%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 2.5 mm²
- 12 AWG
- 20 A
- Breaker
- 1%
- Voltage drop
- 11m
- 3-core to buy
Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.
Heat decides this size: it carries the breaker current without overheating, and the voltage drop is fine.
Cores
3 cores: line, neutral and earth
🛒 To buy: 11 m of 3-core 2.5 mm² cable (your 10 m run plus 10% spare, rounded up).
Which cable
Typical price for 11 m: £23–£50
Fixed wiring clipped to walls indoors.
🔎 Find it onlineMachines, workshops and anything that moves or vibrates.
🔎 Find it onlineRough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
- Check the earth fault loop impedance and the RCD protection required by your local rules.
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.