Cable size for 13 A over 100 m, three-phase

For 13 A over 100 m on a 400 V three-phase supply, use at least 4 mm² (10 AWG) copper cable, protected by a 20 A breaker. Voltage drop: 3.2%.

Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.

The same current over other distances

DistanceCable sizeVoltage drop
10 m2.5 mm² (12 AWG)0.5%
20 m2.5 mm² (12 AWG)1%
30 m2.5 mm² (12 AWG)1.5%
50 m2.5 mm² (12 AWG)2.5%
100 m4 mm² (10 AWG)3.2%
4 mm²
10 AWG
20 A
Breaker
3.2%
Voltage drop
111m
5-core to buy

Say it (“32 amps, three-phase, 40 metres, buried”) or photograph the rating plate. Nothing is stored.

How the cable runs
Use at least4 mm²10 AWG
Breaker20 A
Voltage drop3.2% · 12.67 V
Current13 A
Cable carries up to32 A

The distance decides this size: 2.5 mm² would stay cool enough, but over 100 m it loses too much voltage.

Cores

5 cores: L1, L2, L3, neutral and earth (4 cores if no neutral is needed)

🛒 To buy: 111 m of 5-core 4 mm² cable (your 100 m run plus 10% spare, rounded up).

Which cable

Typical price for 111 m: £580–£1,000

NYM-J / XVB / 5-core LSZH

Fixed wiring clipped to walls indoors.

🔎 Find it online
H07RN-F (rubber, flexible)

Machines, workshops and anything that moves or vibrates.

🔎 Find it online

Rough shop prices in United Kingdom, October 2026. Estimates for budgeting, not quotes; prices change and vary between shops.

  • Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
  • Check the earth fault loop impedance and the RCD protection required by your local rules.

Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.