Cable size for 100 A over 10 m, DC
For 100 A over 10 m on a 24 V DC supply, use at least 70 mm² (2/0 AWG) copper cable, protected by a 125 A fuse. Voltage drop: 2.7%.
Assumes copper cable clipped to a wall (or flexible battery cable for DC), 30 °C, PVC insulation. Change anything below.
- 70 mm²
- 2/0 AWG
- 125 A
- Fuse
- 2.7%
- Voltage drop
- 11 m
- 2-core cable
How the cable runs
Use at least70 mm²2/0 AWG
Fuse125 A
Voltage drop2.7% · 0.64 V
Current100 A
Cable carries up to315 A
The distance decides this size: 25 mm² would stay cool enough, but over 10 m it loses too much voltage.
Cores
2 cores (+ and −), or two single cables, red and black
Which cable
Tinned flexible battery cable (ISO 6722 / SAE J1127)
Vans and boats: resists vibration and corrosion.
Welding cable (H01N2-D)
Very flexible, for heavy battery and inverter leads.
- Several circuits bundled together carry less each: allow for grouping (IEC 60364-5-52 Table B.52.17).
Guidance based on IEC 60364-5-52 for copper cables. Always check against your local rules (BS 7671, NEC, NF C 15-100, RTIEBT…) and the cable maker’s data.