F2

Motor starter planner

Starters for three-phase motors (direct-on-line, star-delta, forward/reverse): the breaker, contactors, overload setting and cable, with the power and control drawing.

Type of starter

Say it (“7.5 kW motor, 400 volts, 25 metres in conduit, star-delta”) or photograph the motor plate. Nothing is stored.

Add to the control circuit

Tap to add or remove. The drawing, parts and steps follow.

Main breaker · Q116 A D
Contactor · KM112 A
Overload relay · F29–13 Aset to 9.6 A
Motor cable4 × 1.5 mm²Voltage drop 0.8% while running

Power and control drawing

Power circuitControl circuitL1L2L3PE123456Q116 A D123456KM112 A AC-3123456F29–13 A→ 9.6 AMotor cable4 × 1.5 mm²15 mU1V1W1M3~M15.5 kW9.6 AL1NQ26 A · 280 VLN9596F21112S1STOP1314S2START1314KM1A1A2KM1280 VH1Running9798F2H2TrippedWireTheSun · DOL

How it works

  1. Press START (S2): the contactor coil KM1 gets power, its three main contacts close and the motor runs. The green lamp H1 lights.
  2. The contactor’s own contact KM1 13–14 bridges START, so the motor keeps running when you let go.
  3. Press STOP (S1): the coil loses power, the contacts open and the motor stops.
  4. If the motor is overloaded, F2 opens 95–96 and stops it, and 97–98 lights the amber lamp H2. Find the cause, then press RESET on F2.

What to buy

  • 13-pole breaker, curve D, 16 A (Q1)$16–$49
  • 1Contactor 12 A (AC-3), 280 V coil, with a normally open auxiliary contact (KM1, e.g. LC1D12)$16–$43
  • 1Thermal overload relay 9–13 A, set to 9.6 A (F2, e.g. LRD16)$22–$49
  • 12-pole breaker 6 A, curve C, for the control circuit (Q2)$9–$27
  • 1 + 1Push buttons: red STOP, normally closed (S1), and green START, normally open (S2)$9–$27
  • 1 + 1Pilot lamps: green “running” (H1) and amber “tripped” (H2)$6–$22
  • 1Enclosure with DIN rail, IP65$27–$76
  • 1Lockable 3-pole isolator next to the motor, 16 A$16–$43
  • 17 m1.5 mm² 4-core cable (3 phases and earth), starter to motor$28–$64
  • 1Control wire 1 mm², ferrules, glands and terminals$11–$27
  • Total (typical)$160–$430

Typical shop prices where you are (October 2026), as a range: estimates for budgeting, not quotes. Installation labour is not included.

  • No plate current given: 9.6 A is typical for a 5.5 kW motor at 480 V. Use the plate value if you have it.
  • When it starts, the motor draws about 67 A for a few seconds. The curve D breaker rides through this; lights on the same supply may dim.
  • The control circuit works at 280 V between a phase and neutral. Without a neutral, use a 480 V coil between two phases or a control transformer.
  • A motor protection breaker (MPCB) can replace Q1 and F2 together: pick one whose range holds 9.6 A.
  • Fit a lockable isolator next to the motor if it is out of sight of the starter, so nobody can start it while it is being worked on.
  • If the motor turns the wrong way, swap any two of the three phases at the motor.