- 9.6 A
- Motor current
- 16 A
- Q1
- 12 A
- KM1
- 9.6 A
- F2
Motor starter planner
Starters for three-phase motors (direct-on-line, star-delta, forward/reverse): the breaker, contactors, overload setting and cable, with the power and control drawing.
Type of starter
Say it (“7.5 kW motor, 400 volts, 25 metres in conduit, star-delta”) or photograph the motor plate. Nothing is stored.
Add to the control circuit
Tap to add or remove. The drawing, parts and steps follow.
Main breaker · Q116 A D
Contactor · KM112 A
Overload relay · F29–13 Aset to 9.6 A
Motor cable4 × 1.5 mm²Voltage drop 0.8% while running
Power and control drawing
How it works
- Press START (S2): the contactor coil KM1 gets power, its three main contacts close and the motor runs. The green lamp H1 lights.
- The contactor’s own contact KM1 13–14 bridges START, so the motor keeps running when you let go.
- Press STOP (S1): the coil loses power, the contacts open and the motor stops.
- If the motor is overloaded, F2 opens 95–96 and stops it, and 97–98 lights the amber lamp H2. Find the cause, then press RESET on F2.
What to buy
- 13-pole breaker, curve D, 16 A (Q1)$16–$49
- 1Contactor 12 A (AC-3), 280 V coil, with a normally open auxiliary contact (KM1, e.g. LC1D12)$16–$43
- 1Thermal overload relay 9–13 A, set to 9.6 A (F2, e.g. LRD16)$22–$49
- 12-pole breaker 6 A, curve C, for the control circuit (Q2)$9–$27
- 1 + 1Push buttons: red STOP, normally closed (S1), and green START, normally open (S2)$9–$27
- 1 + 1Pilot lamps: green “running” (H1) and amber “tripped” (H2)$6–$22
- 1Enclosure with DIN rail, IP65$27–$76
- 1Lockable 3-pole isolator next to the motor, 16 A$16–$43
- 17 m1.5 mm² 4-core cable (3 phases and earth), starter to motor$28–$64
- 1Control wire 1 mm², ferrules, glands and terminals$11–$27
- Total (typical)$160–$430
Typical shop prices where you are (October 2026), as a range: estimates for budgeting, not quotes. Installation labour is not included.
- No plate current given: 9.6 A is typical for a 5.5 kW motor at 480 V. Use the plate value if you have it.
- When it starts, the motor draws about 67 A for a few seconds. The curve D breaker rides through this; lights on the same supply may dim.
- The control circuit works at 280 V between a phase and neutral. Without a neutral, use a 480 V coil between two phases or a control transformer.
- A motor protection breaker (MPCB) can replace Q1 and F2 together: pick one whose range holds 9.6 A.
- Fit a lockable isolator next to the motor if it is out of sight of the starter, so nobody can start it while it is being worked on.
- If the motor turns the wrong way, swap any two of the three phases at the motor.
Guidance only. A motor starter must be installed, tested and checked by a qualified electrician.